- Keep the Emergency Stop switch in DG panel in released condition.
- In DG panel keep the Selector switch in "Local" mode.
- Keep DG and EB ACB in "LOCAL" mode in relevant MDB.
- Ensure the Lube oil level is with in the allowable limit.
- Check day tank diesel level (above 75%).
- Keep the radiator water upto the Brim.
- Keep the batteries in fully charged condition.
- If power fails switch on the DG ACB by Turn the "TNC" switch to Close position
- Check D.G Output Voltage,Load Current,Frequency,Water Temp,Lube oil Pressure,Battery Voltage and Day tank diesel level.
Stopping procedure for Diesel Generators in "Manual" mode
- Ensure the E.B. voltage is with in the limit i.e.,10 kv to 11.5kv.
- Close the SF6 breaker of relevant Transformer.
- Now Switch off the ACB of relevant DG and Close the relevant transformer ACB.
- After 60 Seconds, switch off the Engine.